Sertim logo
zipper technik
homezipper protectionothers tubingclipsreferencescontact french
Other Kind of Tubing Protections» Metallic and Plastic Conduit » Shieldtite      
arrow Metalic and Plastic Conduit
  • Shieldtide
"Metallic and Plastic Conduit"
Jewel of the range, SEALTITE conduit are build from a flexible galvanized steel core conduit, square-locked with cord packing and thermoplastic cover.
It is a high tech patent manufacture.


SHIELDTITE: EMI / EMP shielding.

shieltide
pdf
back

The SHIELDTITE conduit has been developed according to MIL-STD 1310D (military standard USA) and has an inter-locked construction with a bronze core.
This results in excellent shielding against electromagnetic fields, which is one of the most occurring disturbing factors of electronic equipment.
To exclude any disturbances in your data-transport or apparatuses, SHIELDTITE will the best solution.
SHIELDTITE is used in machines and apparatuses, which need to be shielded effectively from EMI and EMP fields, like for example in the military sector, marine and airtraffic controle.
Construction : Bronze core, inter-locked, thermoplastic cover (PVC compound). Cover specifications : PVC, sunlight and UV resistant, suitable for outside installation.
The cover is good resistant against oil and greases.
Temperature : -45ºC to +105ºC, intermittent up to +120ºC.
Colour : Grey.

SEALTITE conduit systems

Inside diameter   mm 12,6 16,1 21,0 26,8 35,1 40,3
Outside diameter   mm 17,8 21,1 26,4 33,1 41,8 47,8
Bending radius static mm 80 90 110 120 135 200
(centerline) dynamic mm 100 125 160 200 240 290
Standard carton   mm 30 30 30 30 15 15
Article no. black     304.012.1 304.016.1 304.020.1 304.026.1 304.035.1 304.040.1

Trade size Sealtite inch 2+ 2.1/2+ 3+ 4+
Fittings ISO M63 - - -
  PG 4B - - -
  NPT 2+ 2.1/2+ 3+ 4+

EN 50086 CLASSIFICATION*1

  Compression resistance Impact resistance Min. temp. Max. temp. Blending resistance Electrical properties
Shieldtide 4 Heavy
(1250 N)
4 Heavy (6J) 4+ -40°C 3 +105°C 4 Flexible 3*2 With electrical continuity and insulating characteristics

  Resistance to ingress of solid objects Resistance to ingress of water Corrosion resistance inside/outside Tensile strength Resistance to flame propagation Suspended load capacity
  6 Dust-tight 7 Protected against the effects of temporary immersion in water; 1m deep, 30 min. 3*3 Medium/high 4 Heavy (1000N) 1 Non-flame propagating 0 None decared

*1 Classification according to EN 50086 is done in combination with the fittings (see catalogue) and also counts as a minimum for the complete range of sizes. Though, for some size in the range a higher classification is possible--> consult your Anamet representative for more information.
*2 Fitting non-insulating.
*3 Based on stainless steel fittings (with standard fittings, class 2 counts for the whole system).
*4 Dynamic applications only at temperatures above 0°C.

EMP SHIELDING (MEOB.96_049 ELM( ADV )).
hft